Chiller maintenance checklist

Free chiller maintenance checklist: lockout, oil, water side and safety cutouts, plus EPA leak rate, leak inspection and record duties for large chillers.

Updated Sources checked

How often: Follow the manufacturer's instructions for the chiller, or the interval set by your organization's maintenance plan. EPA's periodic leak inspections start only after a covered chiller exceeds its leak rate limit.

Sections
9
Checks
67
Critical
2
Sources
96

0/59 answered

0%

Answers, comments and photos stay on this device. Nothing is sent to Irada.

Details such as chiller number or asset tag and plant room, roof or yard where the chiller stands are kept with each inspection you run in Irada. The printout has lines for them.

1

How the chiller rejects heat *

2

Compressor type *

3

What the chiller cools, which sets its EPA leak rate category *

4

Number of independent refrigerant circuits on this chiller *

5

Full charge of this circuit *

lb
6

How the full charge was determined

7

Each person who may open the refrigerant circuit, repair leaks or carry out a leak inspection holds technician certification from an EPA-approved program *

When an item fails

A failed check on a chiller often leads to a refrigerant decision as well as a repair. The owner or operator calculates the leak rate every time refrigerant is added [24], and nobody servicing the chiller may knowingly vent refrigerant to the environment [19].

  • Once the leak rate goes over the threshold for the type of appliance, leaks have to be identified and repaired within 30 days [28], so record the date the rate was found.
  • Lock out the chiller before opening it for repair, and verify isolation before work starts [5].
  • Record what failed, what was repaired and the refrigerant added or recovered, so the next leak rate calculation has the numbers it needs.

Run it with your team in Irada

  • Schedule it per site and assign it to the right people.
  • Turn every failed check into a corrective action that someone else verifies.
  • Keep signatures, photos and the full audit history across sites.
Use this checklist Print with your logo

Answers on this page stay on this device; they are not transferred.

Frequently asked questions

How often should a chiller be serviced?

Follow the manufacturer's instructions and your maintenance plan; the federal refrigerant rules do not set a routine service interval. What they do set is a leak inspection schedule once a covered chiller exceeds its leak rate limit [36]. For a comfort cooling chiller under 40 CFR 82.157 that means once per calendar year [38] until it has not leaked above the limit for one year [39]. Under 40 CFR 84.106 the yearly inspections run from the successful follow-up verification test [82].

Do EPA leak repair rules apply to my chiller?

It depends on the refrigerant and the full charge of each circuit. A circuit with 50 lb or more of class I or class II refrigerant falls under 40 CFR 82.157 [23]. A circuit with 15 lb or more of a regulated HFC or a substitute with a global warming potential above 53 falls under 40 CFR 84.106 [65] [66]. Each independent circuit counts as a separate appliance [6] [59].

What is the allowable leak rate for a chiller?

A chiller used for comfort cooling has a 10 percent limit [27] [72]; EPA lists chillers among comfort cooling appliances [7] [61]. A chiller that is industrial process refrigeration has a 30 percent limit [26] [71]. A chiller serving both counts as industrial process refrigeration when 50 percent or more of its operating capacity goes to the process [14].

What has to happen after a chiller leaks above the limit?

A technician holding EPA technician certification carries out a leak inspection to locate the leaks [30] [74], and the leaks are repaired within 30 days of the refrigerant addition, or 120 days if an industrial process shutdown is needed [29] [73]. An initial verification test follows the repair [32] [76], and a follow-up verification test is done within 10 days of a successful initial test [34] [78].

What records does a chiller owner keep?

The full charge and how it was determined [43] [87], a record of each service that includes the full charge and the leak rate with its method [53] [91], leak inspection records with the date, methods and leak locations [54] [55], and verification test results [56] [95]. Records are kept for at least three years [41] [85].

Do I have to lock out a chiller before maintenance?

OSHA's lockout/tagout standard covers servicing and maintenance where unexpected start-up or release of stored energy could cause injury [1]. The chiller is isolated from its energy source and rendered inoperative first [2], lockout devices are applied by authorized employees [3], and stored energy, such as the charge in drive capacitors, is relieved [4].

Built from 96 official sources

Every check traces to the text it is based on. Read the purpose, how to use it, the rules behind it, what it does not cover and every source.

Guidance, not legal advice. It does not replace the law, the manufacturer's instructions or your organization's competent people, and completing it does not certify that work is safe.