Fire sprinkler inspection checklist

Free fire sprinkler inspection checklist based on OSHA 29 CFR 1910.159: control valves, 18-inch clearance, piping, waterflow alarm and test records.

Updated Sources checked

How often: A main drain flow test every year and the inspector's test valve opened at least every two years. How often to walk the system with this checklist is set by your organization, together with your contractor, insurer and local fire code.

Sections
6
Checks
33
Critical
2
Sources
32

0/27 answered

0%

Answers, comments and photos stay on this device. Nothing is sent to Irada.

Details such as building or site and system, riser or zone inspected are kept with each inspection you run in Irada. The printout has lines for them.

1

Type of system *

2

Was this system installed to meet an OSHA standard? *

3

Number of sprinklers on this system

When an item fails

A failed sprinkler check usually means part of the building is less protected than it should be, so plan for that while the repair happens. The employer keeps the system properly maintained [15], and when the automatic water supply is out of service an auxiliary supply or equivalent protection is provided [22]. Equivalent protection can include a staffed fire watch with extinguishers or hose lines in place, or a secondary water supply [1].

  • Find out which areas the failed valve, pipe or head serves before deciding on the interim protection.
  • Schedule the maintenance for a time when as few people as possible are exposed to the fire hazard [2].
  • Record when protection was reduced, what interim protection was in place and when the system was restored.

Run it with your team in Irada

  • Schedule it per site and assign it to the right people.
  • Turn every failed check into a corrective action that someone else verifies.
  • Keep signatures, photos and the full audit history across sites.
Use this checklist Print with your logo

Answers on this page stay on this device; they are not transferred.

Frequently asked questions

How often does a fire sprinkler system need to be inspected?

For a system installed to meet an OSHA standard, the federal rule sets two intervals: a main drain flow test every year [13] and opening the inspector's test valve at least every two years [14]. Inspection intervals beyond that come from your contractor's program, your insurer and your local fire code.

Does OSHA 1910.159 apply to every sprinkler system?

No. It applies to systems installed to meet a particular OSHA standard [6]; systems installed in workplaces but not required by OSHA are exempt from that section [8]. Older systems installed to the NFPA or NBFU standard in effect at the time are accepted [7]. Whatever the reason a system was installed, the exit route rule still expects safeguards such as sprinkler systems to be in proper working order [32].

How much clearance is needed below sprinkler heads?

At least 18 inches (45.7 cm) of vertical clearance between the sprinklers and material below [9]. Building members and contents should also cause a minimum of interference to the discharge pattern [10], so check new racks, partitions and ducts as well as stack height. Your local fire code may set a larger clearance for some storage.

What do we do when the sprinkler system is shut off?

Provide an auxiliary water supply or equivalent protection while the automatic water supply is out of service [22]; systems of 20 or fewer sprinklers are excepted [23]. OSHA's guidance says equivalent protection may include a staffed fire watch with extinguishers or hose lines, or a secondary water supply [1]. Tell your fire alarm company, insurer and local fire department as your procedures and local code direct.

When is a sprinkler waterflow alarm needed?

On every system with more than 20 sprinklers [30]. The alarm sounds an audible signal on the premises when water flows through the system at the rate of a single sprinkler [31].

Can maintenance staff replace a damaged sprinkler head?

Only approved sprinklers may be used on the system [27], and older style sprinklers may not replace standard sprinklers without a complete engineering review [28]. Given these limits, good practice is to leave replacement to your fire protection contractor.

Built from 32 official sources

Every check traces to the text it is based on. Read the purpose, how to use it, the rules behind it, what it does not cover and every source.

Guidance, not legal advice. It does not replace the law, the manufacturer's instructions or your organization's competent people, and completing it does not certify that work is safe.